Powered by Google translate

Please note we have enabled Google translate for your country.

This is a machine translation, and may not be perfect in all cases.

You can turn this off at any time, and return to the original English by selecting “English” at the top of the drop down menu.

Power Factor Correction Transformers (PFC’s)

Worked Example of  Suitable Tests

Power Factor Correction Transformers Overview

The sheer volume of SMPS (Switch Mode Power Supplies) produced each year, and the combination of legislation and consumer pressure for lower running power usage has driven an increase in the use of power factor correction (PFC) inductors. As their name suggests, PFC’s are used to optimize the power factor of SMPS’s to improve energy efficiency, and lower power consumption.

PFC’s broadly fall to two categories; Passive and Active

In a Passive PFC circuit an inductor is used on the input to a SMPS, in conjunction with capacitors to correct the power factor.
However, the advantage of simpler components is often offset by the larger component size needed to operate at 50/60Hz and the theoretical limit of performance of around PF= 0.75.

Much more common are Active PFC circuits, where the PFC inductors and capacitors are deployed after the Diode Bridge, and actively switched using a control circuit. The increasing reliability and decreasing cost of IC’s for this purpose have made Active PFC the predominant method. This also results in smaller components (as the switching frequency is higher) and better performance with PF typically >0.9

cooper CTX16-15954

 

Eaton manufacture a range of PFC inductors for the active method in their CTX range.

Here we will demonstrate a possible AT test solution for their part # CTX16-15954

 

Transformer schema

Suggested Testing for PFCs

AT Editor Schematic for PFCs

The transformer is shown here, converted into an AT EDITOR test program schematic.
It is important to note that the windings on pins 1-4 and 2-5 are actually physically terminated independently, and thus are represented and tested as separate windings.

A Voltech DC1000 was also connected to pins 2-5 and controlled by the AT test program as the part also requires its inductance testing under 3.1 Amps DC Bias current

AT Editor Schematic for PFCs

PFCs - AT Fixturing

The conventional 5mm pin terminations make the CTX16-15954 ideal for fixturing using Kelvin pins.

This gives a very quick piece-fit time, and the advantage of 4 wire Kelvin measurements for accurate resistance measurements, as all effects due to fixture wiring and contact resistance can be compensated out of measurements.

PFC fitted to Voltech Fixture
PFC fitted to Voltech Fixture
PFC removed showing orientation pins
PFC removed showing orientation pins
PFC fixture  - top view
PFC fixture - top view
PFC fixture  - top view close up
PFC fixture - top view close up

PFCs - AT Test Program

The test program first checks the DC resistance of each winding individually to check for continuity, and also as a check of correct wire gauge.

Next the Turns ratio is checked. As there are 3 windings, two turns ratio tests are required to prove all windings. a) From one of the primaries to the secondary, and b) from one primary to one secondary.

Then the series inductance is measured to check the operation of the core material, and then (using the DC1000), 3.1A DC is applied as per the spec, and the inductance is checked to prove that the core has not saturated.

Finally, the isolation is proved by a Hi Pot test between both the primaries and the secondary winding.

#

Test

Description

Pins and Conditions

Reason

1 R DC resistance Pins 1-4, limit set to < 0.760 Ohms, as published spec of 0.380 Ohms is for both windings in parallel. To check the winding resistance is below a maximum. Also acts as a check of correct wire gauge and good termination.
2 R DC resistance Pins 2-5, limit set to < 0.760 Ohms as published spec of 0.380 Ohms is for both windings in parallel. To check the winding resistance is below a maximum. Also acts as a check of correct wire gauge and good termination.
3 R DC resistance Pins 9-7, limit set to < 0.212 Ohms, as per spec. To check the winding resistance is below a maximum. Also acts as a check of correct wire gauge and good termination.
4 TR Turns Ratio Energize pins 1:4 100mV 10 kHz, measure 1-4 to 7-9 to be 1:0.082 +/- 3% To check correct turn ratio P1:S1
5 TR Turns Ratio Energize pins 1:4 100mV 10 kHz, measure 1-4 to 2-5 to be 1:1 +/- 3% To check correct turn ratio P1:P2
6 LS Series Inductance Pins 1-4. 100mV, 10 kHz, limits 0.9 mH to 1.1 mH as per datasheet spec. To check the correct number of turns and correct operation of the core material
7 LSBX Series Inductance with DC Bias Pins 2-5, 100mV, 10 kHz with 3.1 A DC bias applied as per part specification. Limits set to 0.75 mH minimum Checks that cores does not saturate in presence of 3.1 A DC bias.
8 HPAC Hi Pot AC 1500 V for 1 second, pins 1,2,4,5 LO to pins 7,9,Hi. Limit 20 mA Check isolation of transformer. Note that the pins with the DC1000 connected are kept on the LO side of the hi pot test.
        AT5600 Run time 3.79 sec
        (AT3600 Run time 5.84 sec)

NOTES:

As the LSBX (testing the part under the presence of 3.1 A DC) result is largely dependent on core material, users may prefer to execute this test periodically, rather than on every transformer to save time. The AUDIT test feature of the AT5600 will allow you test (and still retain test results) for a chosen sample of the batch.

Similarly, the HPAC testing shown matches the declared specification. Again, customers may wish to use the AUDIT function to periodically test HPAC for a longer dwell time.

AT Test Results for PFCs